Air conditioning and fluorinated gases: maintenance obligations
Published on Updated on
By Feliorbe team
Quick answer
In Portugal, air conditioning, refrigeration and heat pump equipment containing fluorinated gases is governed by Regulation (EU) 2024/573 and Decreto-Lei n.º 145/2017. Equipment containing 5 tonnes of CO2 equivalent or more must be checked for leaks at least every 12 months (every 24 months with a leak detection system), and more often above 50 and 500 tonnes. Only certified technicians and companies may work on it, and the operator keeps the records for at least five years and reports the annual data to the APA (Agência Portuguesa do Ambiente, the Portuguese Environment Agency) by 31 March.
What rules apply to fluorinated gases in Portugal?
Regulation (EU) 2024/573 and Decreto-Lei n.º 145/2017 apply. The European regulation, of 7 February 2024, entered into force on 11 March 2024 and repealed Regulation (EU) No 517/2014; the Portuguese decree-law ensures its implementation in Portugal.
Decreto-Lei n.º 145/2017, of 30 November, was written for the old regulation, but it is still the basis used by the Agência Portuguesa do Ambiente (APA, the Portuguese Environment Agency) for the annual reporting of data. Article 37(5) of the new regulation handles the transition: references to the repealed regulation ‘shall be construed as references to this Regulation’. An official document from December 2025 states that the decree-law is ‘currently under review’ and names the Agência para o Clima (ApC, the Portuguese Climate Agency) as the competent authority; the APA's fluorinated gas pages are moving to the ApC website.
| Legislation | What it establishes |
|---|---|
| Regulation (EU) 2024/573 | Prevention of emissions, leak detection, records, recovery, certification and restrictions on use |
| Decreto-Lei n.º 145/2017 | Reporting of data to the APA, national certification, intervention sheet, enforcement and administrative offences |
| Implementing Regulation (EU) 2024/2215 | Types of certificate for technicians and certification requirements for refrigeration, air conditioning and heat pump companies |
Who is the operator of the equipment: the maintenance company or the customer?
By default, it is the customer who owns the equipment. The APA explains that, ‘unless contractual provisions state otherwise, the owner of the equipment is responsible for complying with the applicable legal provisions’.
The operator is whoever exercises ‘actual power over the technical functioning’ of the equipment. According to the APA, the owner's obligations can be transferred to the maintenance company, but only ‘through clear contractual provisions’, which must state explicitly who carries out the work, keeps the records and reports the data to the authorities. Article 5(2) of Decreto-Lei n.º 145/2017 provides the same for data reporting, which can be handled by another person ‘namely by contract’.
Which equipment must be checked for leaks?
Equipment that contains 5 tonnes of CO2 equivalent or more of the fluorinated gases listed in Annex I to the regulation, or 1 kg or more of the gases in Section 1 of Annex II (Article 5(1) of Regulation (EU) 2024/573).
The obligation covers, among others, stationary refrigeration equipment, air conditioning equipment and heat pumps (Article 5(2)). Hermetically sealed equipment, labelled as such, is exempt if it contains less than 10 tonnes of CO2 equivalent of Annex I gases or less than 2 kg of gases in Section 1 of Annex II. In residential buildings, hermetically sealed and labelled equipment is exempt if it contains less than 3 kg of fluorinated gases.
The charge in tonnes of CO2 equivalent depends on the gas: the same quantity in kilograms can fall above or below the threshold. The APA provides a converter for this calculation.
How often must leak checks be carried out?
It depends on the charge of the equipment. Article 5(6) of Regulation (EU) 2024/573 sets the minimum intervals, which are doubled when the equipment has a leakage detection system installed:
| Charge (Annex I gases) | Charge (Section 1 of Annex II) | Without detection system | With detection system |
|---|---|---|---|
| From 5 to less than 50 t CO2 eq. | From 1 to less than 10 kg | Every 12 months | Every 24 months |
| From 50 to less than 500 t CO2 eq. | From 10 to less than 100 kg | Every 6 months | Every 12 months |
| 500 t CO2 eq. or more | 100 kg or more | Every 3 months | Every 6 months |
Three obligations complete this schedule:
- Mandatory leakage detection system on stationary refrigeration, air conditioning and heat pump equipment with 500 t CO2 eq. or more (or 100 kg or more of gases in Section 1 of Annex II), checked at least every 12 months (Article 6(1) and (3)).
- Check after a leak is repaired, carried out by a certified technician ‘no sooner than 24 hours of operation and no later than one month after the repair’ (Article 4(5)).
- Check after installation or retrofitting of equipment, with a record kept for at least five years (Article 8 of Decreto-Lei n.º 145/2017).
Who can work on the equipment?
Only certified technicians who belong to certified companies. Article 13(1) of Decreto-Lei n.º 145/2017 applies this rule to leak checking, recovery, installation, repair, maintenance and decommissioning that involve contact with the gas, ‘regardless of the charge they contain’.
Article 10 of Regulation (EU) 2024/573 requires certification of natural persons (paragraph 1) and of companies that install, service, repair or decommission this equipment (paragraph 2). Implementing Regulation (EU) 2024/2215, which repealed Implementing Regulation (EU) 2015/2067, defines the types of certificate for technicians:
| Certificate | Activities covered |
|---|---|
| A1 | All activities with fluorinated gases and hydrocarbons |
| A2 | The same, limited to equipment with a charge of less than 3 kg (or less than 6 kg if hermetically sealed and labelled) |
| B | All activities with carbon dioxide (CO2) |
| C | All activities with ammonia (NH3) |
| D | Recovery of gases from equipment with less than 3 kg (or less than 6 kg if hermetically sealed and labelled) |
| E | Leak checking, without breaking into the refrigeration circuit |
Certificates issued under the old regulation ‘shall remain valid’ (Article 10(9) of Regulation (EU) 2024/573), but technicians will have to take refresher training or an assessment process at least every seven years, for the first time by 12 March 2029 at the latest. For the customer, a practical rule: under Article 10(12), a company may only entrust these tasks to another ‘after having verified’ that it holds the necessary certificates.
What records must be kept?
The operator keeps, for each piece of equipment subject to leak checks, a record of the gases, the work carried out and the checks, for at least five years. The maintenance company keeps a copy of the same records for the same period (Article 7(2) of Regulation (EU) 2024/573).
Under Article 7(1), the record states:
- the quantity and type of gases contained in the equipment, including the quantity added during installation;
- the quantity of gases added during servicing or because of leaks, with the date;
- the quantity of gases recovered;
- whether the gases added were recycled or reclaimed, and by which facility;
- the identity of the company and the technician who did the work, with the certificate number;
- the dates and results of leak checks and repairs;
- if the equipment was decommissioned, the measures taken to recover and dispose of the gases.
The APA provides a template, the Registo da Aplicação/Equipamento (RAE, the application/equipment record): one record per independent refrigeration circuit, updated at every intervention that affects the parts containing fluorinated gases. In addition, for every intervention with a risk of leakage, the technician must ‘keep a copy of the intervention sheet for at least five years’ (Article 21(1) of Decreto-Lei n.º 145/2017).
What must be reported to the APA, and by when?
By 31 March each year, the operator of equipment subject to leak checks reports the data for the previous year, using the fluorinated gases form in SILiAmb (the APA's online environmental reporting platform) (Article 5(1) of Decreto-Lei n.º 145/2017). HVAC maintenance companies report their purchases and sales of fluorinated gases by 30 June (Article 5(4)).
The 31 March report states, in kilograms and by gas, the quantity held on 1 January, the quantity acquired for recharging, the quantity contained in equipment acquired and the quantity recovered for recharging, recycling, reclamation or destruction. When the owner is an individual, this report is only required if they have entrusted it to another person, for example by contract (Article 5(3)). The APA states that reporting after 31 March is a minor environmental administrative offence.
For the 30 June report, entities that supply or acquire gases keep records of buyers and sellers for at least five years (Article 6 of the decree-law). The European regulation also requires gas suppliers to keep a record of each buyer's certificate number and the quantities purchased (Article 7(3)).
What happens to gas removed from equipment?
It must be recovered by a certified technician and recycled, reclaimed or destroyed. Article 8(1) of Regulation (EU) 2024/573 places this obligation on the operator, and Article 4(1) prohibits intentional release into the atmosphere where it is not technically necessary.
Recovered gas may only be used to refill equipment if it has been recycled or reclaimed (Article 8(6)). At the end of the equipment's life, the operator must call on a certified technician to ensure the gases are recovered and, if necessary, sent on for treatment (Article 19(1) of Decreto-Lei n.º 145/2017). Temporary storage of the gas as waste ‘may not exceed 90 days’ (Article 19(3)).
Which gases can no longer be used for servicing?
Since 1 January 2026, Annex I fluorinated gases with a global warming potential (GWP) of 2,500 or more can no longer be used to service air conditioning equipment and heat pumps (Article 13(4) of Regulation (EU) 2024/573). In refrigeration, the same ban has applied since 1 January 2025 (Article 13(3)).
Until 1 January 2032, in existing air conditioning equipment and heat pumps, it is still possible to use reclaimed gases, in labelled containers, or recycled gases, recovered from such equipment and used by the company that recovered them or by the company on whose behalf the recovery was carried out. From 1 January 2032, the ban extends to gases with a GWP of 750 or more for servicing stationary refrigeration equipment, except chillers (Article 13(5)). Before proposing a repair, it is worth confirming the gas in the equipment and its GWP.
How do you organise air conditioning maintenance day to day?
For an HVAC company, the hard part is meeting the check intervals across dozens of units, with different charges and deadlines, and making sure every job leaves a record.
- Set out in the contract who the operator is, who keeps the records and who reports the data to the APA, as the APA recommends.
- Link each contract to the check interval that matches the charge of the equipment.
- Assign visits to technicians certified for the activities involved.
- Close each job with a report and photos, so the equipment's history is complete.
In Feliorbe's Contracts module, each maintenance contract has a plan with a frequency, assigned technicians and visits generated automatically up to the end date. In Schedule and jobs, the technician follows a checklist with measurements, before and after photos and a job report. See how it works for HVAC companies or request a demo. Compliance with legal obligations remains the responsibility of the operator and the certified company.
Sources
- Regulamento (UE) 2024/573 do Parlamento Europeu e do Conselho, de 7 de fevereiro de 2024, relativo aos gases fluorados com efeito de estufa [Regulation (EU) 2024/573 on fluorinated greenhouse gases] (EUR-Lex)
- Regulamento de Execução (UE) 2024/2215 da Comissão, de 6 de setembro de 2024 — Certificação de pessoas singulares e coletivas (equipamentos fixos de refrigeração, ar condicionado e bombas de calor) [Commission Implementing Regulation (EU) 2024/2215: certification of natural and legal persons for stationary refrigeration, air conditioning and heat pump equipment] (EUR-Lex)
- Decreto-Lei n.º 145/2017, de 30 de novembro — Execução do regulamento relativo aos gases fluorados com efeito de estufa [implementation of the fluorinated greenhouse gases regulation] (Diário da República)
- Agência Portuguesa do Ambiente — Gases fluorados: legislação [fluorinated gases: legislation]
- Agência Portuguesa do Ambiente — Operadores de equipamentos com gases fluorados [operators of equipment containing fluorinated gases]
- Agência Portuguesa do Ambiente — Equipamentos fixos de refrigeração, ar condicionado e bombas de calor [stationary refrigeration, air conditioning and heat pump equipment]
- Agência Portuguesa do Ambiente — Comunicação de dados no SILiAmb [reporting data in SILiAmb]
- Agência Portuguesa do Ambiente — Compra e venda de gases fluorados [purchase and sale of fluorinated gases]
- Agência para o Clima — Procedimento para o reconhecimento da certificação obtida noutro Estado-Membro [recognition of certification obtained in another Member State] (dezembro de 2025)
This guide is for information only and is not a substitute for legal advice.
Frequently asked questions
How often must an air conditioning unit be checked for leaks?
It depends on the gas charge. Under Article 5 of Regulation (EU) 2024/573, equipment containing 5 to less than 50 tonnes of CO2 equivalent is checked at least every 12 months; 50 to less than 500 tonnes, every 6 months; 500 tonnes or more, every 3 months. With a leak detection system installed, the intervals are doubled.
Who is responsible for the fluorinated gas obligations: the customer or the maintenance company?
By default, the owner of the equipment, as the operator. The APA states that these obligations, including the records and data reporting, can be transferred to the maintenance company through clear contractual arrangements.
By when must fluorinated gas data be reported to the APA?
By 31 March each year, for the previous year's data on equipment subject to leak checks (Article 5(1) of Decreto-Lei n.º 145/2017). HVAC maintenance companies report their purchases and sales of fluorinated gases by 30 June (Article 5(4)).
Do you need to be certified to service air conditioning?
Yes, for work that involves contact with the gas. Article 13 of Decreto-Lei n.º 145/2017 reserves it for certified technicians belonging to certified companies, whatever the charge of the equipment, and Article 10 of Regulation (EU) 2024/573 requires the certification of technicians and companies.