Skip to content
Feliorbe

Fire extinguisher maintenance: legal obligations in Portugal

Published on Updated on

By Feliorbe team

Quick answer

In Portugal, fire extinguishers may only be serviced by a company registered with the ANEPC (the National Emergency and Civil Protection Authority) (Article 23 of Decreto-Lei n.º 220/2008), with its service certified to the NP 4413 standard (Portaria n.º 773/2009). Responsibility for the extinguishers lies with the owner, the operator of the premises or the condominium. Each maintenance action is entered in the safety records, kept for at least 10 years (Article 201 of the Regulamento Técnico de SCIE, the technical regulation on fire safety in buildings).

What legislation governs fire extinguishers in Portugal?

Fire extinguishers are part of the legal regime for fire safety in buildings (SCIE, segurança contra incêndio em edifícios). The regime is set out in Decreto-Lei n.º 220/2008, of 12 November (a Portuguese decree-law), and the technical rules in the Regulamento Técnico de SCIE (the technical regulation on fire safety in buildings), approved by Portaria n.º 1532/2008, of 29 December (a ministerial order).

This guide covers mainland Portugal: the Autonomous Regions of the Azores and Madeira may have their own rules.

Both instruments are still in force, but they have been amended:

LegislationWhat it establishesMain amendments
Decreto-Lei n.º 220/2008Legal regime for SCIE: responsibilities, self-protection measures, registration of companies, inspections, administrative offencesDecreto-Lei n.º 224/2015, Decreto-Lei n.º 95/2019 and Lei n.º 123/2019, which republished it
Portaria n.º 1532/2008Regulamento Técnico de SCIE: technical conditions, equipment and self-protectionPortaria n.º 135/2020, of 2 June, which republished it
Portaria n.º 773/2009, of 21 JulyRegistration with the ANEPC of companies that sell, install and maintain equipmentPortaria n.º 208/2020, of 1 September, which republished it

Portaria n.º 135/2020 did not replace the 2008 regulation: it amended and republished it. References in this guide to an ‘article’ of the technical regulation are to the version republished in 2020.

Who is responsible for the fire extinguishers in a building?

The owner, whoever operates the premises or, for the common parts, the condominium or the managing body. The maintenance company carries out the service, but legal responsibility for safety conditions lies with the customer.

Article 6 of Decreto-Lei n.º 220/2008 assigns this responsibility ‘throughout the entire life cycle’ of buildings:

  • Housing (use type I): the owner; for the common parts of a building under horizontal property (a building divided into separately owned units), the condominium (paragraph 3);
  • Other uses: the owner, if the building is in their possession; whoever runs the premises; or the body that manages the common areas (paragraph 4).

This person or body is the ‘person responsible for safety’ (RS, responsável pela segurança) referred to in Article 194 of the technical regulation. Under Article 20 of the decree-law, they appoint a safety delegate to carry out the self-protection measures, but remain ‘fully bound’ to comply with the SCIE conditions.

Where are fire extinguishers required, and how many?

As a rule, the distance from any exit of a risk area to the nearest extinguisher may not exceed 15 metres. Article 163 of the technical regulation applies to all use types, except housing in the 1st and 2nd risk categories.

In the absence of another justified criterion, Article 163(2) requires extinguishers to be calculated at the rate of:

  • 18 litres of standard extinguishing agent per 500 m² (or part thereof) of floor area;
  • one extinguisher per 200 m² of floor (or part thereof), with a minimum of two per floor.

Extinguishers must be signposted, in unobstructed places, on a bracket or in a dedicated recess, with the handle at a height ‘no more than 1.2 m above the floor’ (paragraph 3). Kitchens and laboratories that are risk C areas must also have fire blankets and, where oils or fats are used, an extinguisher with a minimum rating of 25F (paragraph 5).

The technical regulation defines an extinguisher as a device that must be ‘in conformity with the standards EN 3, EN 1866 and NP 4413’ (Annex I, Article 8(9)).

Who can maintain fire extinguishers?

Only a company registered with the ANEPC and, for extinguishers, with its service certified to the NP 4413 standard. Without these two requirements, the maintenance is an administrative offence.

Article 23 of Decreto-Lei n.º 220/2008 states that entities that sell, install or maintain SCIE equipment and systems ‘are subject to registration with the ANEPC’ (Autoridade Nacional de Emergência e Proteção Civil, the National Emergency and Civil Protection Authority), without prejudice to other licences required by law. Extinguishers are on the list of equipment in Article 2 of Portaria n.º 773/2009, alongside, for example, fire detection, emergency lighting and safety signs.

There is a specific requirement for extinguishers: the registration application includes a copy of the certificate issued by a body accredited by the IPAC (Instituto Português de Acreditação, the Portuguese accreditation body) for entities ‘subject to mandatory certification for extinguisher maintenance (NP 4413)’ (Article 5(2)(c) of Portaria n.º 773/2009). In the wording republished by Lei n.º 123/2019, Article 25 of the decree-law makes it an administrative offence for extinguishers to be maintained ‘by entities whose service is not certified in accordance with NP 4413’.

Before hiring a company, the customer can check it on the ANEPC website, which publishes the registration details (Article 3(4) of the Portaria).

How does a fire extinguisher company register with the ANEPC?

By application to the president of the ANEPC, through the ANEPC's IT system, with the certificate of commercial registration, the declaration of start of activity, the NP 4413 certificate and the details of the responsible technician. Registration is subject to a fee.

Under Article 5 of Portaria n.º 773/2009, as worded by Portaria n.º 208/2020, the application includes:

  • the certificate from the Conservatória do Registo Comercial (the Commercial Registry Office) showing that the company's object includes selling, installing or maintaining SCIE equipment;
  • a copy of the certificate issued by a body accredited by the IPAC (mandatory for extinguisher maintenance);
  • the declaration of start of activity;
  • the details of the responsible technician, and proof of their technical ability and appropriate professional training.

The responsible technician plans, organises and controls the quality of the service and coordinates the operating technicians. They sign a statement of responsibility for installation or maintenance (Article 6). If the company is left without a responsible technician, the registration is suspended until the situation is resolved (Article 9(2)).

Once registered, any change to the company's details must be notified to the ANEPC within 10 days at most (Article 8). The registration remains valid as long as the company carries on the activity and meets the requirements (Article 9(1)).

How often must fire extinguishers be maintained?

At the intervals set in the maintenance programme, in accordance with the NP 4413 standard that applies to extinguishers. The decree-law does not set the schedule: it refers to the technical standards and requires maintenance to follow a programme with dates.

Article 202(4) of the technical regulation states that the upkeep and maintenance of equipment and systems must be ‘based on programmes setting out schedules and lists of periodic verification tests’.

What the law penalises is delay. In the wording republished by Lei n.º 123/2019, Article 25 of the decree-law makes it an administrative offence to have extinguishers ‘whose expiry or maintenance dates have passed’, as well as the absence or poor maintenance of extinguishers.

NP 4413 is a Portuguese standard that is not freely available. The deadlines for each operation (maintenance, recharging, testing, end of life) and the rules for the label placed on the extinguisher should be checked against the text of the standard in force, available from the Instituto Português da Qualidade (IPQ, the Portuguese Quality Institute), or with the body that certifies the company.

What are safety records?

They are the archive in which the person responsible for safety keeps inspection reports, anomalies and all maintenance work on safety equipment. They must be kept for at least 10 years.

Article 21 of Decreto-Lei n.º 220/2008 includes safety records among the self-protection measures. Article 201 of the technical regulation details what they must contain, among other things:

RecordWhat it includes
External reportsSurveys, inspections and checks, including those by the authorities
AnomaliesDescription, impact, date detected and how long the repair took
Maintenance work‘item worked on, type of and reason for the action taken, date and person responsible’
IncidentsFalse alarms, incipient fires, fire brigade call-outs
Training and drillsBrief reports on the training sessions and exercises

Records are archived ‘for a minimum period of 10 years, on paper or in digital form’ (Article 201(2)). For the customer, the report of each visit by the maintenance company is part of these records: it should state which device was worked on, what was done, when and by whom.

Who carries out inspections, and what happens in case of non-compliance?

The ANEPC and, for the 1st risk category, the municipalities. Buildings are also subject to regular inspections, requested by the person responsible for safety.

Article 24 of Decreto-Lei n.º 220/2008 gives enforcement powers to the ANEPC, to the municipalities (1st risk category) and to ASAE (the Food and Economic Safety Authority) as regards the placing of equipment on the market. Under Article 19, regular inspections are mandatory, at the request of the person responsible, at the following maximum intervals:

Risk categoryMaximum interval
1st6 years
2nd5 years
3rd4 years
4th3 years

Excluded are the 1st risk category use types, except types IV and V, and residential-only buildings in the 2nd category (paragraph 5). After an inspection, the person responsible must correct the non-conformities within the deadlines set in the report (paragraph 7).

Article 25 lists the administrative offences, including maintenance without registration with the ANEPC, missing or out-of-date safety records and failure to notify the ANEPC of changes to the registration. Check the amount of the fines in the consolidated version of the decree-law in the Diário da República (Portugal's official gazette).

How do you organise fire extinguisher maintenance day to day?

For a fire extinguisher company with hundreds of customers, the risk is a date that passes without anyone noticing. And without a complete report of each visit, the customer has no proof for their safety records.

  • One date per customer, in one place: the maintenance interval belongs in the contract, not in a spreadsheet.
  • Visits planned in advance, so no extinguisher goes past its date.
  • The same procedure on every visit, with the same steps for every technician.
  • One report per visit, with what was done, the date and the technician, delivered to the customer for their safety records.

In Feliorbe, the Contracts module holds each customer's plan, price and frequency and generates the visits automatically. In Schedule and jobs, the technician follows the step-by-step checklist, closes the job with before and after photos, and the report is linked to the customer's record. See how fire extinguisher and fire safety companies work or request a demo. Registration with the ANEPC, NP 4413 certification and compliance with the obligations remain the responsibility of the company and its customers.

Sources

This guide is for information only and is not a substitute for legal advice.

Frequently asked questions

Who may service fire extinguishers in Portugal?

A company registered with the ANEPC for fire extinguisher maintenance (Article 23 of Decreto-Lei n.º 220/2008), with its service certified to NP 4413 by a body accredited by the IPAC (the Portuguese Accreditation Institute) (Article 5 of Portaria n.º 773/2009, as amended by Portaria n.º 208/2020).

Who is responsible for the maintenance of a building's fire extinguishers?

The owner, whoever operates the premises or, in the common parts, the condominium or the managing body (Article 6 of Decreto-Lei n.º 220/2008). The maintenance company provides the service, but responsibility for the safety conditions lies with the customer.

How long must fire extinguisher maintenance records be kept?

At least 10 years, on paper or in digital format. Article 201 of the Regulamento Técnico de SCIE includes in the safety records a list of all maintenance actions, with the item worked on, the type of and reason for the action, the date and the person responsible.

How many fire extinguishers are mandatory per floor?

In the absence of another justified criterion, one for every 200 m² of floor or unit, with a minimum of two per floor, and 18 litres of standard extinguishing agent per 500 m², no more than 15 metres from any exit of a risk area (Article 163 of the Regulamento Técnico de SCIE).

See Feliorbe in action

We show you the platform using your business's own cases. Online demo, with no commitment.

Request a demo